EXIT AND EMERGENCY LIGHTING INSTALLATION AND CHECKING - MACKAY, PAGET AND NORTHERN BEACHES
At TGA Electrical we understand how important it is to maintain a safe and compliant workplace. That's why we offer emergency and exit light testing, repairs, and upgrades to businesses throughout Mackay, Paget and the surrounding areas.
​
You can rest assured that your emergency and exit lighting systems are in good hands. We offer a wide range of services to ensure that your lights are always up-to-date and functioning correctly, including:
-
Testing and inspections
-
Repairs and maintenance
-
Upgrades and installations
​
The Australian Building Codes stipulate that emergency and exit lighting installed in public buildings is required to be maintained to current AS/NZS 2293.1:2018. This includes periodic maintenance and inspection procedures outlined in AS/NZ 2293.2:1995 essential to ensuring emergency evacuation lighting systems are in a state of readiness for operation at all times.
Our team of licensed electricians has years of experience working with emergency and exit lighting systems. We use state-of-the-art equipment to ensure that your lights are functioning correctly, and we can quickly identify any issues that may arise.
HOW IS EMERGENCY LIGHTING TESTING CARRIED OUT?
This is a test that certifies all the Exit & Emergency lights are in good working order and that the batteries sustain their charge for 90 minutes during a power blackout or building fire
Six Monthly Tests
-
Visual checks of all Emergency and Exit lights for mains operation.
-
Check for operation of maintained exit lights and replace faulty lamps prior to testing where required.
-
Isolate power to all exit and emergency lights, in most cases either by utilising the test switch or turning off the circuit breaker that supplies power to the fittings
-
To meet the Australian Standards AS2293 / BCA requirements, a discharge test will last for a duration of 90 minutes.
-
After tests have been completed the tester must restore the system to normal operation.
-
Those units which have failed the discharge test must be either repaired and restored to normal condition or replaced.
-
Lamp replacement of any defective lamps shall be replaced. All lamps should be replaced on a yearly or after 10,000 of operation.
Twelve Monthly Procedures
-
Carry out all checks as per six-monthly procedures.
-
Clean and Inspect fittings and clean reflective surfaces as necessary on all emergency and exit lighting diffusers as required
-
Visual checks to ensure that the emergency lighting system operates in correct relationship to the normal lighting in any designated area.